Customization: | Available |
---|---|
Type: | Hv & Mv |
Structure: | Double-column Disconnector |
Still deciding? Get samples of US$ 450/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Pole-mounted Air/Load breaker switch
The (H)GW series outdoor Air/Load breaker switch is a three-phase AC 50Hz /60Hz outdoor medium-voltage switchgear, which can open and close the power line and can see the obvious disconnect distance.
Application voltage levels include 12kV, 24kV and 36kV.
Application standard: IEC62271-102
Item | Unit | Data | ||
Rated voltage | kV | 12 | 24 | 36 |
Rated frequency | Hz | 50/60 | ||
Rated current | A | 400 / 630 | ||
Rated short-circuit withstand/breaking current | kA | 12.5 | ||
Rated short-circuit making current (peak) | kA | 31.5 | ||
Rated peak withstand current | kA | 31.5 | ||
Rated short-circuit time | Sec | 1 | ||
Mechanical Operations | Times | 5000 | ||
Power frequency withstand voltage (1 min) | kV | 28/32 | 50/60 | 70/80 |
Lightning impulse withstand voltage (peak) | kV | 76/85 | 125/145 | 170/190 |